Solenoid Valve Parts and Components

Introduction

A solenoid valve pairs electrical control with mechanical flow regulation. That's why you find it in automation lines, pneumatic equipment, process systems, and press machinery.

You might need to name a part, understand what moves, pick a replacement, or trace a fault. The trouble is that component names and construction change from one valve design to the next, and visually similar parts often aren't interchangeable.

This guide covers the actuator, valve body, sealing and pilot components, operating types, and selection and troubleshooting.

Key Takeaways

  • Every solenoid valve has an electromagnetic actuator and a valve body that controls the media path.
  • The coil moves the plunger; springs, seats, seals, and diaphragms decide how flow opens or closes.
  • Parts differ across direct-acting, pilot-operated, NC, NO, latching, and multi-port designs.
  • Replace parts only after matching the model number, media, pressure, voltage, and seal material.

What Is a Solenoid Valve and How Does It Work?

ASCO defines a solenoid valve as an electromagnet and core combined with a valve body containing one or more orifices. Core movement permits or stops flow when the solenoid is energized or de-energized. It controls liquids, gases, and compressed air.

Two assemblies do the work:

  • Solenoid actuator: converts electrical energy into linear mechanical movement.
  • Valve body: holds the ports, flow passages, orifice, seat, and sealing elements.

When the coil is energized, magnetic force must overcome the return spring, friction from sliding fits, and, depending on the design, fluid pressure. When power drops, the spring (or a latching mechanism) determines the resting state.

A permanent-magnet latching valve needs only a momentary pulse to change state. It holds that state with no continuous voltage, even through a power loss.

A normally closed cycle

  1. De-energized: the spring holds the seal against the seat. No flow.
  2. Energized: the coil pulls the plunger up, lifting the seal off the seat. Flow opens.
  3. De-energized again: the magnetic field collapses and the spring drives the valve shut.

Solenoid Valve Parts and Components

Solenoid actuator components

The coil is insulated copper wire wound on a bobbin or core tube. Voltage, AC or DC design, insulation, and duty cycle all affect operation. Duty ratings are variant-specific: Burkert's Type 0331 brass and stainless variants are rated for 100% continuous duty, while its 8 W PEEK variant is rated for 60% over 30 minutes.

The plunger (also called the armature or core) is the moving ferromagnetic part. It transfers magnetic force to the valve mechanism.

The armature tube guides the plunger and separates the electrical actuator from the media. Burkert describes it as a precision-machined, nonmagnetic-steel tube, so a clean, aligned bore matters.

Spring and magnetic circuit components

The return spring sets the de-energized position. In a normally closed valve it presses the seal onto the seat; in a normally open valve it holds the seal away.

Supporting magnetic parts include:

  • Fixed core or stopper, which completes the magnetic circuit and limits stroke
  • Plunger stop, which improves repeatability
  • AC shading ring, which keeps the core from releasing at the alternating-voltage zero crossing and reduces humming (DC coils don't need one)

Valve body and flow-control components

The valve body is the pressure-containing structure with inlet, outlet, and internal passages. Type 0331 offers brass, stainless steel, PEEK, and polypropylene bodies. Those are product options, not universal compatibility endorsements.

The orifice is the controlled opening. The seat is the stationary sealing surface that a disc, poppet, plunger seal, or diaphragm closes against.

A stem, disc, poppet, or piston carries plunger motion to the flow-control point. The exact arrangement depends on whether the valve is direct-acting, diaphragm-operated, or piston-operated, and spec details for these parts vary by model.

Sealing and pilot components

Seals, O-rings, and diaphragms prevent leakage between chambers and along the flow path. Material choice depends on the medium and temperature. Burkert's chemical resistance chart shows why names alone don't settle it:

Material Long-term temperature guidance Mineral oil
NBR -10 to +90 °C Suitable
EPDM -30 to +130 °C Unsuitable
FKM 0 to +150 °C Suitable
PTFE -20 to +200 °C Suitable

Temperature and concentration change resistance, so treat the chart as guidance and confirm against the valve datasheet.

Pilot-operated valves add a pilot hole, a bleed passage, and a diaphragm or piston. The pilot vents the upper chamber, line pressure lifts the main element, and the bleed passage restores pressure above it for closure. A small solenoid force ends up controlling a much larger flow path.

Three-step pilot-operated solenoid valve flow control sequence

Electrical and external interface components

External parts handle power, protection, and installation:

  • Lead wires, terminals, and DIN connectors (Burkert's Type 2508 is Form A to DIN EN 175301-803, rated IP65)
  • Coil housings and enclosures
  • Manual overrides for startup and testing
  • Mounting features

Enclosure ratings can depend on assembly. Festo specifies its VSVA as IP65 / NEMA 4 only in combination with a plug socket.

How Solenoid Valve Components Work Together

Direct-acting valve operation

In a direct-acting valve, coil force moves the plunger or poppet straight against the seat. No pressure differential is needed to move a diaphragm.

ASCO's direct-acting designs operate from 0 psi up to their rated maximum, so they suit low or zero differential pressure. Always check flow and pressure limits on the manufacturer datasheet.

A diaphragm doesn't make a valve pilot-operated. Type 0331 is direct-acting yet uses a diaphragm to isolate the coil system from the medium.

Pilot-operated valve operation

A pilot-operated valve uses a small pilot opening and line pressure to move a diaphragm or piston over the main orifice. The sequence:

  1. The plunger opens the pilot path.
  2. The upper chamber relieves toward the outlet.
  3. Line pressure lifts the diaphragm or piston, opening the main passage.

Before you rely on pilot operation, verify:

  • Minimum differential pressure
  • Media cleanliness
  • Pilot passage condition
  • Flow direction

Requirements vary: ASCO separates floating pilot elements, which need a minimum pressure drop, from mechanically hung elements that open at zero.

Sealing, return, and failure behavior

Coil, plunger, spring, seat, seal, and body must stay aligned for reliable shutoff. Symptoms point toward, but don't prove, component causes:

  • Leakage: worn seal or damaged seat
  • Won't open: low voltage, stuck plunger, or low differential pressure
  • Won't close: debris on the seat or a weak spring
  • Buzzing or overheating: shading ring problems, wrong voltage, or a stalled plunger

Parker Sporlan's 2024 service instructions list plunger stalling and mechanical interference among coil-burnout causes. They also warn against energizing a coil that isn't mounted on the valve.

Fail position matters too. Normally closed (NC), normally open (NO), and latching designs react differently to power loss, so pick the one that matches the machine's safety and process requirements.

Solenoid Valve Types and Component Variations

Operating principle versus resting state

These classifications answer different questions and aren't interchangeable:

  • Direct-acting vs. pilot-operated: the first uses coil force alone; the second adds a diaphragm, pilot passage, or piston and usually needs a minimum pressure differential.
  • NC, NO, latching: describes the state when de-energized, or after a momentary signal.

Solenoid valve operating principle and resting state classifications

Ways and positions

Ways describe ports; positions describe switching states.

Configuration Typical use
2/2 Basic on/off
3/2 Supply, output, exhaust; single-acting cylinder
4/2 Double-acting cylinder, one side pressurized while the other vents
5/2, 5/3 Separate exhaust paths for each output; 5/3 adds center-position variants

Pneumatic versus hydraulic

Pneumatic valves such as the Festo VSVA run on compressed air with specified air quality. Hydraulic valves such as Parker's D3W use a wet-armature solenoid and spool, with separate port and tank-pressure limits.

Seals, bodies, and contamination tolerances differ, so never swap parts between media systems without verifying compatibility.

Selecting, Maintaining, and Troubleshooting Components

Selecting replacement parts or a complete valve

Confirm these before ordering:

  • Media type, pressure range, and differential
  • Flow capacity (Cv) and port size
  • Coil voltage, frequency, and tolerance (Type 0331 specifies ±10%)
  • Duty cycle and operating temperature
  • Body and seal material
  • Normal state and enclosure rating

Start with the model number, nameplate, parts diagram, and datasheet. Burkert requires original spare parts ordered by spare-set designation plus device identification number, because kit contents differ by variant. Parts that look alike can differ in dimensions, spring force, voltage, or material.

Inspection and troubleshooting

Work safely first:

  1. De-energize power.
  2. Isolate the media supply.
  3. Depressurize and vent the lines.
  4. Apply lockout/tagout, then verify isolation.
  5. Follow manufacturer instructions before disassembly.

Five-step solenoid valve inspection safety isolation procedure

OSHA's lockout/tagout standard states that push buttons and selector switches are not energy isolating devices.

Then match symptoms to areas:

  • Electrical faults: coil wiring and supply voltage
  • Sticking: plunger movement and armature-tube cleanliness
  • Leakage: seals and seats
  • Pilot failures: pilot holes and pressure differential

Burkert's Type 6213/6281 manual lists a blocked diaphragm control bore as a fault cause and calls for an upstream dirt trap of 500 micrometers or finer on those models.

Integration with industrial automation

In press and machine automation, solenoid valves perform the pneumatic functions while electronic controls decide when each receives a command. Pressroom Electronics supplies control-reliable controls for dual-solenoid pneumatic and hydraulic valve applications in metal stamping and forming.

Frequently Asked Questions

What are the main components of a solenoid valve?

Coil, plunger or armature, spring, armature tube, valve body, ports, orifice, seat, and seals. Pilot-operated designs add a diaphragm or piston and pilot passages.

What is the moving part of a solenoid called?

It's commonly called the plunger, armature, or core. It moves in response to the magnetic field the coil generates.

What are the two types of solenoid valves?

It depends on the classification. Direct-acting versus pilot-operated describes the operating mechanism, while normally closed versus normally open describes the de-energized state.

How does a normally closed solenoid valve differ from a normally open valve?

A normally closed valve blocks flow when de-energized and opens when powered. A normally open valve flows when de-energized and closes when powered.

What should you check when selecting replacement solenoid valve parts?

Match the model number, coil voltage, media, pressure, temperature, flow, seal material, dimensions, and ports. Confirm everything against the manufacturer's documentation.